Himoinsa PowerCube

400-700 kVA Compact Generator set

Three phase | 50/60 Hz | Diesel

By using the “Request Quote” (RFQ) button below, we understand that you are simply requesting a quotation for a price for this product. You are not entering into a contract with Midas and are not committing to a purchase. Once we receive your RFQ, we will contact you using the contact details you provide. We look forward to hearing from you.

View Quote Request List
SKU: N/A Category: Tag:
Phase

Three Phase

Model

HPCW-420 T5, HPCW-420 T5, HPCW-505 T5, HPCW-510 T5, HPCW-660 T5, HPCW-390 T6, HPCW-465 T6, HPCW-520 T6, HPCW-620 T6

Hz

50 Hz, 60 Hz



1. RADIATOR IN COMPARTMENT ISOLATED FROM THE ENGINE

2. INTERNAL SILENCER

3. FULL ACCESS FOR ENGINE AND ALTERNATOR MAINTENANCE

4. CONTROL PANEL

5. POWER OUTPUT

6. FULL ACCESS FOR RADIATOR MAINTENANCE

Technical Specifications:


– Container version.
Soundproofing provided by high-density volcanic rock wool
High mechanical resistance
Low level of noise emissions
System of interior lighting
Door with window to visualize control panel, alarms and measurements
Reinforced lifting points for crane hoisting and lower ones for transportation by forklift
Residential steel silencer with -35dB attenuation and tilting cap in the exhaust
Anti-vibration shock absorbers
Steel chassis
Manual oil extraction pump
Robust construction designed for continuous or emergency applications
Stainless steel fittings
Emergency stops
Easy access to the power connection
Reinforced chassis for heavy range
Silent-block with anti-corrosion protection between the genset and the chassis
Easy access to fill radiator through the roof
50L tank for automatic oil replenishment
10-foot container
External connection to fuel tank
3-way valve for external fuel supply (available in 1/2″ and 3/8″ fittings)
– Electrical System Container.
Battery charger
Heating resistor
Control panel and emergency stop button
Power panel
Battery charge alternator with ground connection
Starter battery/ies installed (cables and bracket included)
Ground connection electrical installation with connection ready for ground spike (not supplied)
4 pole circuit breaker
Power panel with safety protection in output terminals box (open thermal magnetic protection and alarm)
Maintenance-free and anti-explosion battery
Battery isolator


– EXHAUST SYSTEM.
Maximum exhaust temperature: 445 ºC
Exhaust Gas Flow: 0,613 kg/s
Maximum allowed back pressure: 50 mbar
Heat dissipated by exhaust pipe: 703 KCal/Kwh
– NECESSARY AMOUNT OF AIR.
Intake air flow: 1770 m3/h
– STARTING SYSTEM.
Starting power: 6 kW
Starting power: 8,16 CV
Recommended battery: 185 x 2 Ah
Auxiliary Voltage: 24 Vdc
– FUEL SYSTEM
Fuel Oil Specifications: Diesel
Fuel Tank: 500 L


– Dimensions.
Length: 2.991 mm
Height: 2.591 mm
Width: 2.438 mm
Maximum shipping volume: 18,89 m3
Weight with liquids in radiator and sump: 6.651 kg
Fuel tank capacity: 500 L

Himoinsa Powercube Datasheet


    Go to Top